GP-4100 Series Hardware Manual
4-10
Power Cord Specifications
Power Connector (Plug) Specifications
WARNING
HAZARD OF ELECTRIC SHOCK
Prior to connecting the GP unit's power cord terminals to the power terminal block, confirm that the
GP unit's power supply is completely turned OFF, via a breaker, or similar unit.
Supplying a power voltage other than that specified will damage the power source and the GP unit.
Since there is no power switch on the GP unit, be sure to attach a breaker-type switch to its power
cord.
When the FG terminal is connected, be sure the wire is grounded.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
When the FG terminal is connected, be sure the wire is grounded. Not grounding the
GP unit will result in excess noise and vibration.
The SG and FG terminals are connected internally in the GP unit.
When connecting the SG wire to another device, be sure that the design of the
system/connection does not produce a shorting loop.
Power Cord Diameter 0.75 to 1.5mm
2
(18-16AWG)
Conductor Type Simple or Twisted Wire
Conductor Length
Use copper conductors only.
If the Conductor’s end (individual) wires are not twisted correctly, the end wires may
either short against each other, or against an electrode.
+
24V
-
0V
FG
FG Grounding Terminal connected to the
GP
7mm
[0.3in.]
Insertion
Direction
+
-
FG